A simulation study of several schematic models of both water- and air-cooled single-effect LiBr-H2O absorption chillers energized by a high-potential, low-temperature (73 degrees C) geothermal source has been carried out using IPSEpro refrigeration software package. All the simulated models were validated against a lithium bromide-water pressure-temperature DUhring chart. The results obtained show that when the coefficient of performance, heat input into the generator, and cooling mass flowrates are fixed, the cycle parameters are highly affected by variation of the coolant temperature. This information will be useful to designers of absorption refrigeration systems.
Author(s): Masheiti S, Agnew B
Publication type: Article
Publication status: Published
Journal: Proceedings of the Institution of Mechanical Engineers, Part A: Journal of Power and Energy
Year: 2010
Volume: 224
Issue: A7
Pages: 947-955
Print publication date: 01/01/2010
ISSN (print): 0957-6509
ISSN (electronic): 2041-2967
Publisher: Professional Engineering Publishing Ltd.
DOI: 10.1243/09576509JPE916