Toggle Main Menu Toggle Search

Open Access padlockePrints

The operational performance of Scottish minewater-based ground source heat pump systems

Lookup NU author(s): David Banks

Downloads

Full text for this publication is not currently held within this repository. Alternative links are provided below where available.


Abstract

Two open-loop, minewater-based, ground source heating schemes have been operating since 1999-2000 in Scotland (UK), at Shettleston (Glasgow) and near Cowdenbeath (Fife). In both cases, ferruginous water is pumped from flooded coal mine workings via a borehole, circulated through the evaporator of the heat pump and reinjected via a shallower borehole to Carboniferous strata. The heat is delivered to a water-based thermal store providing central heating for apartment complexes and contributing to domestic hot water. It is demonstrated, via hydrochemical analysis and speciation modelling of the Fife minewater, that the success of the schemes is due to lack of contact between minewater and the atmosphere (thus limiting degassing of CO2 and absorption of O-2). Indeed, recent difficulties with one of the schemes are ascribed to vandalism of the recharge main allowing access to oxygen, causing precipitation of ferric oxyhydroxide and clogging of the recharge borehole.


Publication metadata

Author(s): Banks D, Pumar AF, Watson I

Publication type: Conference Proceedings (inc. Abstract)

Publication status: Published

Conference Name: Quarterly Journal of Engineering Geology and Hydrogeology: Minewater 2008 Conference

Year of Conference: 2009

Pages: 347-357

ISSN: 1470-9236

Publisher: Geological Society Publishing House

URL: http://dx.doi.org/10.1144/1470-9236/08-081

DOI: 10.1144/1470-9236/08-081

Library holdings: Search Newcastle University Library for this item

ISBN: 20414803


Share